| Sign In | Join Free | My futurenowinc.com |
|
Model Number : SXCY
Impulse Energy : 7.31~320kJ
MOQ : 1 Set
Total Impulse Capacitance : 0.1625~0.0833μF
Brand Name : Sansion
Test Waveform : Lightning & Switching Impulse
Delivery Time : 30 Working Days
Payment Terms : T/T,L/C
Stage Voltage : ±100~±200kV
Packaging Details : Plywood Case
Certification : CE/SGS/EMS/ISO 9001
Stage Structure : 1~24 Stages
Place of Origin : China
Max Rated Voltage : ±4800kV
The SXCF Series Impulse Voltage Generator is designed for high-voltage impulse testing of electrical equipment under lightning and switching overvoltage conditions.
It supports lightning impulse full-wave, chopped-wave, and switching impulse voltage tests, and can generate eight standard impulse waveforms, including lightning, switching, oscillating, steep-front, and transformer induced switching waves.
With technical parameters compliant with Chinese national standards and IEC standards, the SXCF Series provides a reliable solution for insulation performance testing of high-voltage electrical equipment.
Test Objects: Power transformers, high-voltage insulators, HV cables, surge arresters, switchgears, CT/PT, bushings and other high-voltage equipment.
Application Sites: High-voltage laboratories, third-party testing institutes, electrical equipment factories and power grid research centers.
Testing Purposes: Type testing and routine factory testing.
| Rated Voltage(kV) | Total Impulse Capacitance(μF) | Stage Capacitance(μF) | Impulse Energy(kJ) | Stage Voltage(kV) | No. of Stages |
|---|---|---|---|---|---|
| ±100~±400 | 0.1625~0.0833 | 0.325~0.5 | 7.31~33.74 | ±100 | 1~4 |
| ±300~±900 | 0.1625~0.0833 | 0.325~0.5 | 7.31~33.74 | ±150 | 2~6 |
| ±1050~±1500 | 0.0464~0.05 | 0.325~0.5 | 25.58~56.25 | ±150 | 7~10 |
| ±1600~±2400 | 0.0625~0.0833 | 0.5~1 | 80~240 | ±200 | 8~12 |
| ±2800~±3200 | 0.0357~0.0625 | 0.5~1 | 80~240 | ±200 | 14~16 |
| ±3600~±4800 | 0.0278~0.03125 | 0.5~1 | 140~320 | ±200 | 18~24 |
1. What is the working principle of the SXCY Impulse Voltage Generator?
The impulse generator stores electrical energy in multiple impulse capacitors and releases the stored energy through controlled triggering and series discharge to produce a high-voltage impulse.
2. How many stages are available?
The SXCY Series can be configured with different numbers of stages according to the required output voltage. The product range shown includes configurations from 1–4 stages up to 18–24 stages.
3. What impulse energy can the system provide?
The listed configurations provide impulse energy ranging from approximately 7.31 kJ to 320 kJ, depending on the rated voltage, capacitance and number of stages.
4. What is the capacitor configuration?
The system uses impulse capacitors together with grading capacitors and wave-shaping components. Capacitor values are selected according to the required voltage and impulse waveform.
5. Why is low inductance important in an impulse generator?
Low inductance in the return circuit helps reduce unwanted circuit effects during the very rapid impulse discharge process, supporting more accurate and stable waveform generation.
|
|
Lightning Impulse Voltage Generator HV Surge Impulse Test Set for Substation Equipment & High Voltage Switchgear Test Images |